Toshiba GRL100-701B Instruction Manual page 420

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

Transmission data
Sending side
12 bits × (Ia, Ib, Ic)
Phase current
Positive-sequence
A-MODE: V1 fixed. 4 bits / 1 frame (sent
Voltage
it by 3 frame shared)
B-/GPS-MODE: V1 for OST/FL. If the
OST/FL are not used, the
following are configurable.
V.COM1-S (Signal No.: 2096)
V.COM2-S (Signal No.: 2097)
V.COM3-S (Signal No.: 2098)
S.V.COM1-S (Signal No.: 2100) to
S.V.COM12-S (Signal No.: 2111)
Zero-sequence
A-MODE: I0 fixed. 4 bits / 1 frame (sent it
current
by 3 frame shared)
B-/GPS-MODE: I1 for DIFG is assigned.
If the DIFG is not used, the
following are configurable.
I.COM1-S (Signal No.: 2112)
I.COM2-S (Signal No.: 2113)
I.COM3-S (Signal No.: 2114)
S.I.COM1-S (Signal No.: 2116) to
S.I.COM12-S (Signal No.: 2127)
COM1 – COM3
A-MODE: DIF-A, -B, -C for model 513
fixed. For other models, these
are configurable.
COM1-S (Signal No.: 2048)
COM2-S (Signal No.: 2049)
COM3-S (Signal No.: 2050)
COM4, COM5
Used for transfer signals.
(85S1, 85S2)
COM4-S (Signal No.: 2051)
COM5-S (Signal No.: 2052)
SUB2-COM
B-/GPS-MODE: RA∗ for RYIDSV is
(CBDS/RA1)
assigned. If RYIDSV is not
used, the following are
configurable.
SUB2_COM1-S (Signal No.: 2064) to
SUB2_COM12-S (Signal No.: 2075)
SP2/RA2
SUB3_COM1-S (Signal No.: 2080) to
SUB3_COM12-S (Signal No.: 2091)
SA
Configurable data.
SUB_COM1-S (Signal No.: 2056) to
SUB_COM5-S (Signal No.: 2060)
Table N-1
User Configurable data
Receiving side
12 bits × (Ia, Ib, Ic)
A-MODE: V1 fixed. 4 bits / 1 frame (sent it by 3 frame shared)
B-/GPS-MODE: V1 for OST/FL. If the OST/FL are not used, the following
are configurable.
V.COM1-R1 (Signal No.: 960) / V.COM1-R2 (Signal No.: 976)
V.COM2-R1 (Signal No.: 961) / V.COM2-R2 (Signal No.: 977)
V.COM3-R2 (Signal No.: 962) / V.COM3-R2 (Signal No.: 978)
S.V.COM1-R1 (Sig. No.: 964) to S.V.COM12-R1 (Sig. No.: 975) /
S.V.COM1-R2 (Sig. No.: 980) to S.V.COM12-R2 (Sig. No.: 991)
A-MODE: I1 fixed. 4 bits / 1 frame (sent it by 3 frame shared)
B-/GPS-MODE: I1 for DIFG. If the DIFG are not used, the following are
configurable.
I.COM1-R1 (Signal No.: 992) / I.COM1-R2 (Signal No.: 1008)
I.COM2-R1 (Signal No.: 993) / I.COM2-R2 (Signal No.: 1009)
I.COM3-R2 (Signal No.: 994) / I.COM3-R2 (Signal No.: 1010)
S.I.COM1-R1 (Sig. No.: 996) to S.I.COM12-R1 (Sig. No.: 1007) /
S.I.COM1-R2 (Sig. No.: 1012) to S.I.COM12-R2 (Sig. No.: 1023)
COM1-R1 (Signal No.: 1088) / COM1-R2 (Signal No.: 1128)
COM2-R1 (Signal No.: 1089) / COM2-R2 (Signal No.: 1129)
COM3-R1 (Signal No.: 1090) / COM2-R2 (Signal No.: 1130)
The following are signals without two-time verification:
COM1-R1_UF (Sig. No.: 1096) / COM1-R2_UF (Sig. No.: 1136)
COM2-R1_UF (Sig. No.: 1097) / COM2-R2_UF (Sig. No.: 1137)
COM3-R1_UF (Sig. No.: 1098) / COM2-R2_UF (Sig. No.: 1138)
COM4-R1 (Signal No.: 1091) / COM4-R2 (Signal No.: 1131)
COM5-R1 (Signal No.: 1092) / COM5-R2 (Signal No.: 1132)
The following are signals without two-time verification:
COM4-R1_UF (Sig. No.: 1099) / COM4-R2_UF (Sig. No.: 1139)
COM5-R1_UF (Sig. No.: 1100) / COM5-R2_UF (Sig. No.: 1140)
SUB2_COM1-R1 (Sig. No.: 1112) to SUB2_COM12-R1 (Sig. No.: 1123) /
SUB2_COM1-R2 (Sig. No.: 1152) to SUB2_COM12-R2 (Sig. No.: 1153)
SUB3_COM1-R1 (Sig. No.: 1168) to SUB3_COM12-R1 (Sig. No.: 1179) /
SUB3_COM1-R2 (Sig. No.: 1184) to SUB3_COM12-R2 (Sig. No.: 1195)
SUB_COM1-R1 (Sig. No.: 1104) to SUB_COM5-R1 (Sig. No.: 1108) /
SUB_COM1-R2 (Sig. No.: 1144) to SUB_COM5-R2 (Sig. No.: 1148)
 419 
6 F 2 S 0 8 5 0
Remarks
Fixed.
Available for only
A-MODE except for
model 513.
Sent by 12 SSP
cycle.
No. 2058, 2059 and
2060 in
B-/GPS-MODE are
not available.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grl100-702bGrl100-711bGrl100-712b

Table of Contents