Bu_Trip - Toshiba GRL100-701B Instruction Manual

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

Name
5A rating
76
SRCθ
Disable - I
77
PDTD
200 - 2000
78
RYID
79
RYID1
80
RYID2
81
TDSV
100 - 16000
82
TCDT1
-10000 - +10000
83
TCDT2
-10000 - +10000
84
DIF
Off - On
85
STUB
Off - On
86
DIFG
Off - On
87
OST
Off - Trip - BO
88
OCBT
Off - On
89
OCIBT
Off - On
90
MOCI
Long - Std - Very - Ext
91
EFBT
Off - On
92
EFBTAL
Off - On
93
EFIBT
Off - NOD - F - R
94
MEFI
Long - Std - Very - Ext
95
BF1
Off - T - TOC
96
BF2
Off - On
97
BFEXT
Off - On
98
THMT
Off - On
99
THMAL
Off - On
100
TTSW1
Off - Trip - BO
101
TTSW2
Off - Trip - BO
102
RDIF
Off - On
103
OTD
Off - On
104
DIF-FS
Off - OC - OCD ‐ Both
105
DIFG-FS
Off - On
106
INTCOM
Off - On
107
ZS-C
Mho - Quad
108
ZG-C
Mho - Quad
109
BLZONE
COM - IND
110
Z1CNT
1 - 2 - 3 - 4 - 5 - 6
111
Z2TP
Off - On
112
Z3TP
Off - On
113
ZRTP
Off - On
114
PSB-Z1
Off - On
115
PSB-Z2
Off - On
116
PSB-Z3
Off - On
117
PSB-CR
Off - On
118
PSB-ZR
Off - On
119
UVPWIEN
Off - On
120
STUB-OC
Off - On
121
SOTF-DL
CB - UV - Both
122
SOTF-OC
Off - On
123
SOTF-Z1
Off - On
124
SOTF-Z2
Off - On
125
SOTF-Z3
Off - On
126
SOTF-R
Off - On
127
DEF
DEFFEN
Off - On
128
BU-trip
DEFREN
Off - On
129
OVS
OVS1EN
Off - DT - IDMT
130
OVS2EN
Off - On
131
OVG
OVG1EN
Off - DT - IDMT
132
OVG2EN
Off - On
133
UVS
UVS1EN
Off - DT - IDMT
134
UVS2EN
Off - On
135
UVG
UVG1EN
Off - DT - IDMT
136
UVG2EN
Off - On
137 UVS/UVG
VBLKEN
Off - On
138
BCDEN
Off - On
139
Carrier
CRSCM
PUP - POP - UOP - BOP
140
DISCR
Off - On
141
DEFCR
Off - On
142
ZONESEL
143
ECHO
Off - On
144
WKIT
Off - On
145
CH-DEF
CH1 - CH2
146
LSSV
Off - On
147
SVCNT
ALM&BLK - ALM
148
CTSV
Off - ALM&BLK - ALM
149
IDSV
Off - ALM&BLK - ALM
150
CTFEN
Off - On - OPT-On
Range
Units
1A rating
Phase detector selection
us
Permissible telecom. delay time
0 - 63
Relay address (local)
0 - 63
Relay address (remote1)
0 - 63
Relay address (remote2)
us
SV for telecom. delay time
us
CH1 delay time difference
us
CH2 delay time difference
DIF trip
Stub protection
DIFG trip
Out of step trip
OC back-up trip
OCI back-up trip
EF back-up trip
EF back-up trip alarm
EFI back-up trip
CBF re-trip
CBF related trip
CBF initiation by ext. trip
Thermal trip enable
Thermal alarm enable
Transfer trip selection (CH1)
Transfer trip selection (CH2)
Remote differential protection
Oepn terminal detection function
Fail-safe OC use or not
Fail-safe OC use or not
Integral communicarion function use or not
ZS relay characteristic
ZG relay characteristic
Blinder setting mode
Z1 trip mode
Z2 trip enable
Z3 trip enable
ZR trip enable
PSB for Z1 element
PSB for Z2 element
PSB for Z3 element
PSB for carrier trip
PSB for ZR element
Counter measures for overrech of leading phase
at positive phase weak infeed
Stub protection
SOTF condition judged
SOTF OC trip
SOTF Zone1 trip
SOTF Zone2 trip
SOTF Zone3 trip
SOTF Zone-R trip
Forward DEF back-up trip enable
Reverse DEF back-up trip enable
OVS1 enable
OVS2 enable
OVG1 enable
OVG2 enable
UVS1 enable
UVS2 enable
UVG1 enable
UVG2 enable
UV block enable
Broken conductor enable
Carrier protection mode
Distance carrier protection enable
DEF carreir protection enable
Z2 - Z3
Carrier control element
ECHO carrier send
Weak carrier trip
DEF carrier channel setting
LS monitoring
Super visor control
CT supervison control
Id monitoring control
CTF detect.function use or not
 355 
Default Setting of Relay Series(5A rating / 1A rating)
Contents
2C B-ARC , NO -FD , W i t h D i st ance
2TERM
701
702
--
ALM&BLK
6 F 2 S 0 8 5 0
User
3TERM
Settiing
711
712
I
1000
0
0
0
6000
0
0
On
Off
On
Off
On
On
Std
On
On
NOD
Std
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
Off
On
Mho
Mho
COM
4
On
On
Off
On
On
Off
On
Off
Off
Off
CB
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
POP
Off
Off
Z2
Off
Off
CH1
Off
Off
Off
Off