Routing cables; connecting and installing bus connectors
Table 5-1 In-building cable routing, continued
Cables for ...
DC voltage
( 60 V and 400 V),
unshielded
AC voltage
( 25 V and 400 V),
unshielded
DC and AC voltages
( 400 V), unshielded
DC and AC voltages
( 400 V), unshielded
SINEC H1
5-6
and cables for ...
Bus signals, shielded
(SINEC L1, SINEC L2)
Data signals, shielded
(PG, OP, printers, counter signals etc.)
Analog signals, shielded
DC voltage ( 60 V), unshielded
Process signals ( 25 V), shielded
AC voltage ( 25 V), unshielded
Monitors (coaxial cabling)
DC voltage ( 60 V and 400 V),
unshielded
AC voltage ( 25 V and 400 V),
unshielded
DC and AC voltages ( 400 V), unshielded
Bus signals, shielded
(SINEC L1, SINEC L2)
Data signals, shielded
(PG, OP, printers, counter signals, etc.)
Analog signals, shielded
DC voltage ( 60 V), unshielded
Process signals ( 25 V), shielded
Process signals ( 25 V), shielded
AC voltage ( 25 V), unshielded
Monitors (coaxial cabling)
DC voltage ( 60 V and 400 V),
unshielded
AC voltage ( 25 V and 400 V),
unshielded
DC and AC voltages ( 400 V), unshielded
SINEC H1
Others
route ...
in separate bundles or cable ducts
(no minimum spacing necessary)
in shared bundles or cable ducts
Inside cabinets:
in separate bundles or cable
ducts (no minimum spacing
necessary)
Outside cabinets:
on separate cable trays with
at least 10 cm spacing
Inside cabinets:
in separate bundles or cable
ducts (no minimum spacing
necessary)
Outside cabinets:
on separate cable trays with
min. 10 cm spacing
min. 10 cm spacing
in shared bundles or cable ducts
in shared bundles or cable ducts
in separate bundles or cable ducts
with at least 50 cm spacing
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a