Indirect
With indirect parameterization (FCT = XX), the FB IM308C takes the
parameterization
parameterization data from a parameterization data block and not from the
block parameters.
You must open the parameter data block before calling the FB IM308C.
If the parameter data block is too short, the programmable controller goes to
STOP. All subsequent errors are intercepted by the FB IM308C and output in
the parameter data block.
The parameter data block must be structured as follows:
Table 9-21 Structure of the parameter data block for the FB IM308C
Block parameters
,
The table below shows the meanings of the block parameters which you must
send to the FB IM308C in the STEP 5 application program. You can call the
FB IM308C with direct or indirect parameterization.
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a
IM 308-C – addressing, diagnostics and use of the FB IM308C
Data word
Parameter
DW 0
Reserved
DW 1
DPAD
DW 2
IMST
DW 3
FCT
DW 4
GCGR
DW 5
TYP
DW 6
STAD
DW 7
LENG
DW 8
ERR
Recommended data format
KH
KH
KY
KC
KM
KY
KF
KF
KY
9-37
9