Siemens SIMATIC S5 Manual page 308

Ip 266 positioning module
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

STEP 5 Programming
FB 2: Jog 2 with override specification
When the mode number has been entered into QB 64, input 3.6 is scanned. Select
an override of 50 % or 100 %, depending on the selector switch setting. This
value is entered in QB 67.
START
Enter mode
number into
QB 64
I 3.6
yes
set?
Select 50 %
override and enter
into QB 67
END
9-20
FB 2 - NAME:MO2
Select mode
Override set via selector switch:
Select 100 %
override and enter
into QB 67
M100
L
KB 2
T
QB 64
A
I
3.6
50% / 100%
JC =M100
L
KB 50
50%
T
QB 67
BEU
L
KB 100
100%
T
QB 67
BE
EWA 4NEB 812 6057-02