Setting data
■Input/output variable
Variable
Description
name
PVIN
Process input (Engineering value)
ADVANCE
Advance command
INITSTART
Initial start command
LINKIN
Link input (Indirect address)
CASOUT
Cascade output (unit: %)
PTNEND
Pattern end output
LINKOUT
Link output (Indirect address)
■Public variable (operation constant)
Variable
Description
name
PVSTARTNO
PV Start Search Start Step
PVENDNO
PV Start Search End Step
PRIMARY
Lead FB specified
■Public variable (others)
Variable
Description
name
TCNT
Second counter for minute mode.
TMCNT
Millisecond counter for second mode.
*1 Read or write the variables using a program. They are not displayed in "FB Property" of the engineering tool.
■Tag data
For details on tag data that is read or written with this tag access FB, refer to the following.
Page 550 PGS2
*1
Recommended
Type
range
-32768 to 32767
Input variable
TRUE, FALSE
Input variable
TRUE, FALSE
Input variable
Input variable
0 to 100[%]
Output variable
TRUE, FALSE
Output variable
Output variable
Recommended
Initial value
range
1 to 32
1
1 to 32
32
TRUE: Lead
TRUE
FALSE: Following
Recommended
Initial value
range
0 to 59
0
0 to 999
0
10 LOOP CONTROL OPERATION
10.25 Multi-Point Program Setter (M+P_PGS2_)
Data type
REAL
BOOL
BOOL
DWORD
REAL
BOOL
DWORD
Set by
Data type
User
INT
User
INT
User
BOOL
Set by
Data type
System
INT
System
INT
313