Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 232

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Public variable (operation constant)
Variable
Description
name
MTD
Derivative Gain
DVLS
Large Deviation Alarm Hysteresis
PN
Reverse Action/Direct Action
TRK
Tracking Flag
SVPTN_B0
Setting Value (SV) Used
SVPTN_B1
Setting Value (SV) Pattern
NMAX
Output Conversion High Limit
NMIN
Output Conversion Low Limit
*1 When 1 (tracking is executed) is set to the tracking flag, connect CASOUT_T of the primary loop with the input variable CASIN_T.
■Public variable (others)
• Simulation processing
Variable
Description
name
SIMOUT
Simulation Output
*1 Read or write the variables using a program. They are not displayed in "FB Property" of the engineering tool.
■Tag data
For details on tag data that is read or written with this tag access FB, refer to the following.
Page 507 PIDP
Processing details
■Deviation check
This function block performs deviation check processing.
DVL
0
-DVL
Condition
DVL < |DV|
|DV|  (DVL - DVLS)
DV: Deviation (%), DVLS: Large deviation alarm hysteresis (%), DVL: Deviation limit value (%)
10 LOOP CONTROL OPERATION
230
10.9 Position Type PID Control (Enable Tracking for primary loop/Disable Tracking from secondary loop) (M+P_PIDP_T)
*1
*1
DVLA
DVLA
DVLA
occur
reset
occur
Recommended
range
0 to 9999
0 to 100
0: Reverse action
1: Direct action
0: Not executed
1: Executed
TRUE: Not used
FALSE: Used
TRUE: Not primary MV
FALSE: Primary MV
-999999 to 999999
-999999 to 999999
Recommended
range
NMIN to NMAX
DVLS
t
DVLS
DVLA
reset
Alarm (ALM)
Large deviation (DVLA)
TRUE (Detected)
FALSE (Reset)
Initial value
Set by
8.0
User
2.0
User
0
User
0
User
TRUE
User
TRUE
User
100.0
User
0.0
User
Initial value
Set by
0.0
System
Data type
REAL
REAL
INT
INT
BOOL
BOOL
REAL
REAL
Data type
REAL

Advertisement

Table of Contents