Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 161

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting data
■Input/output variable
Variable
Description
name
MV input
MVD
CASDR_MVIN
MV input for cascade direct
MVN
Output to a module
CASOUT
Cascade output
CASOUT_T
Cascade output (With tracking) (Indirect address)
■Public variable (operation constant)
Variable
Description
name
NMAX
Output Conversion High Limit
NMIN
Output Conversion Low Limit
MVCMP_EN
MV Compensation Execution condition
MV_CMPIN
MV compensation value
MVCMP_MODE
MV Compensation Mode
PREMV_EN
Preset MV Execution condition
PREMV_V
Preset manipulated value
MVHLD_EN
MV hold execution condition
MVTRK_EN
MV Tracking Execution condition
MV_TRKIN
MV tracking input
STP_OTYPE
Output when loop or tag is stopped
SEA_OTYPE
MV output selection at occurrence of SEA
ARW_EX_EN
MV Value Instantaneous Pullback
MVPH
MV internal operation value high limit
MVPL
MV internal operation value low limit
MVREV_EN
MV Reverse Execution condition
FOTS_EN
Tight Shut/Full Open Execution condition
MVFO
Output value for full open
MVTS
Output value for tight shut
9.4 Output Processing-3 with Mode Switching (With Input Addition and Compensation) (M+P_OUT3_)
Recommended
Type
range
-999999 to 999999[%]
Input variable
0 to 100[%]
Input variable
NMIN to NMAX
Output variable
0 to 100[%]
Output variable
0 to 100[%]
Output variable
Recommended
Initial value
range
-999999 to 999999
100.0
-999999 to 999999
0.0
TRUE: Execute
FALSE
FALSE: Stop
-999999 to 999999[%]
0.0
0: Addition
0
1: Replacement
TRUE: Execute
FALSE
FALSE: Stop
0 to 100[%]
0.0
TRUE: Execute
FALSE
FALSE: Stop
TRUE: Execute
FALSE
FALSE: Stop
0 to 100[%]
0.0
0: Hold
0
1: Preset value
0: Hold
0
1: Preset MV output
2: Neither hold nor
preset MV output is
performed.
TRUE: Execute
FALSE
FALSE: Not execute
MH to 999999[%]
100.0
-999999 to ML[%]
0.0
TRUE: Execute
FALSE
FALSE: Stop
TRUE: Execute
FALSE
FALSE: Stop
100 to 125[%]
112.5
-25 to 0[%]
-16.82
Data type
REAL
REAL
REAL
REAL
DWORD
Set by
Data type
User
REAL
User
REAL
User
BOOL
User
REAL
User
INT
User
BOOL
User
REAL
User
BOOL
User
BOOL
User
REAL
User
INT
User
INT
User
BOOL
User
REAL
User
REAL
User
BOOL
User
BOOL
User
REAL
User
REAL
9 I/O CONTROL