Communication Detail Settings - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

13.4.2

Communication detail settings

Make the settings according to the usage environment.
Item
Transmission Speed
Data Bit
Stop Bit
Parity
Retry
Timeout Time
Host Address
Delay Time
POINT
POINT
POINT
(1) Delay Time
(2) Communication interface setting by the Utility
(3) Precedence in communication settings
Description
Set this item when change the transmission speed used for communication
with the connected equipment.
(Default: 9600bps)
Set this item when change the data length used for communication with the
connected equipment.
(Default: 8bit)
Specify the stop bit length for communications.
(Default: 2bits)
Specify whether or not to perform a parity check, and how it is performed
during communication.
(Default: None)
Set the number of retries to be performed when a communication error occurs.
(Default: 3times)
Set the time period for a communication to time out.
(Default: 3sec)
Specify the host address (station No. of the GOT to which the PLC is
connected) in the connected network.
(Default: 0)
Set this item to adjust the transmission timing of the communication request
from the GOT.
(Default: 0ms)
When connecting to the PLC and RS-485, set the delay time to 1ms or more.
The communication interface setting can be changed on the Utility's [Communication
Settings] after writing [Communication Settings] of project data.
For details on the Utility, refer to the following manual.
GOT2000 Series User's Manual (Utility)
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
Range
9600bps,19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
1 to 30sec
0 to 63
0 to 300 (ms)
13.4 GOT Side Settings
13
13 - 11