Mitsubishi Electric Q26UD(E)HCPU User Manual page 506

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Number
Name
Data logging
OFF: Not ended
SM1943
setting No.1
ON: Ended
Data logging end
Data logging
setting No.1
OFF  ON:Triggered
SM1944
Data logging
trigger
Data logging
setting No.1
OFF: Not after trigger
SM1945
After data logging
ON: After trigger
trigger
Data logging
setting No.1
OFF: No error
SM1946
Data logging
ON: Error
error
Data logging
setting No.1
OFF: Not stored
SM1947
Data storage in
ON: Being stored
SD memory card
Data logging
setting No.1
Data logging file
OFF: Not executed
SM1948
transfer
ON: Being executed
execution status
flag
504
Meaning
This relay turns on when data logging is
ended.
[Continuous is set for Logging type]
The corresponding bit turns on when data
logging is ended after data have been written
by the number of storable files (Stop is set for
Operation occurring when number of saved
files is exceeded).
[Trigger is set for Logging type]
The corresponding bit turns on when the
trigger condition is met, data are collected by
the number of set times, and then the data
are written to the SD memory card.
This relay also turns on if an error occurs
during data logging (except data logging
error occurred by the execution of online
change).
• This relay turns on when the specified
trigger condition is met.
• This relay is turned on to meet the trigger
condition.
This relay turns on after trigger logging is
triggered. This relay remains on even after
data logging is completed. This relay turns off
when trigger logging is suspended or
stopped.
This relay turns on if a data logging error
occurs.
This relay is turned off by the registration of
the setting or a stop command from the CPU
Module Logging Configuration Tool.
This relay is on while buffer memory data are
being stored to a SD memory card by data
logging.
• This relay turns on when the data logging
file transfer function is started.
• This relay turns off when the data logging
file transfer function is stopped.
Explanation
(When Set)
change)/U
Corresponding
Set by
Corresponding
ACPU
M9
S (Status
New
change)
S (Status
New
S (Status
New
change)
S (Error)
New
S (Status
New
change)
S (Status
New
change)
CPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
*1
LCPU

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents