Mitsubishi Electric Q26UD(E)HCPU User Manual page 343

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[SP.UNIT LAY ERR.]
• The number of connectable modules has
exceeded 10.
• A module is installed exceeding the I/O points of
4096.
• A module is installed crossing the I/O points of
4096.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[SP.UNIT LAY ERR.]
• The number of connectable modules has
exceeded 40.
• A module is installed exceeding the I/O points of
4096.
• A module is installed crossing the I/O points of
4096.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset
2124
[SP.UNIT LAY ERR.]
• The number of connectable modules has
exceeded 10.
• A module is installed exceeding the I/O points of
1024.
• A module is installed crossing the I/O points of
1024.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[SP.UNIT LAY ERR.]
• The number of connectable modules has
exceeded 30.
• A module is installed exceeding the I/O points of
1024.
• A module is installed crossing the I/O points of
1024.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset
Corrective action
• Reduce the number of connectable
modules to 10 or less.
• Remove the module whose number of
points exceeds 4096 points.
• Replace the last module with the one
whose number of occupied points is within
4096.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your
local Mitsubishi representative.
• Reduce the number of connectable
modules to 40 or less.
• Remove the module whose number of
points exceeds 4096 points.
• Replace the last module with the one
whose number of occupied points is within
4096.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your
local Mitsubishi representative.
• Reduce the number of connectable
modules to 10 or less.
• Remove the module whose number of
points exceeds 1024 points.
• Replace the last module with the one
whose number of occupied points is within
1024.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your
local Mitsubishi representative.
• Reduce the number of connectable
modules to 30 or less.
• Remove the module whose number of
points exceeds 1024 points.
• Replace the last module with the one
whose number of occupied points is within
1024.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your
local Mitsubishi representative.
APPENDICES
LED status,
Corresponding
CPU status
CPU
L26CPU-BT
L26CPU-PBT
L06CPU
L06CPU-P
L26CPU
L26CPU-P
L26CPU-BT
L26CPU-PBT
RUN: Off
ERR.:Flashing
CPU Status:Stop
L02CPU
L02CPU-P
L02SCPU
L02SCPU-P
L02CPU
L02CPU-P
A
341

Hide quick links:

Advertisement

Table of Contents