Mitsubishi Electric Q26UD(E)HCPU User Manual page 485

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

ACPU
Special
Special
Special
Relay after
Relay after
Relay
Conversion
Modification
M9196
SM1196
SM325
M9197
SM1197
M9198
SM1198
M9199
SM1199
*1
The following modules support these areas:
• Universal model QCPU whose serial number (first five digits) is "10102" or later
• Q00UJCPU, Q00UCPU, Q01UCPU
*2
The name, 1 minute clock, is for the special relay (M9034) of the ACPU.
*3
The QCPU and LCPU do not support the use of the A8UPU/A8PUJ.
*4
Modules whose serial number (first five digits) is "16112" or later
Name
Meaning
Operation
OFF: Coil output OFF
output at block
ON: Coil output ON
stop
Switch between
I/O numbers
SM1197
SM1198
to be displayed
blown fuse and
OFF
OFF
X/Y0 to 7F0
I/O module
ON
OFF
X/Y800 to FF0
verification error
OFF
ON
X/Y1000 to 17F0
display
ON
ON
X/Y1800 to 1FF0
Data recovery of
OFF: Data recovery
online sampling
disabled
trace/status
ON: Data recovery
latch
enabled
Details
Selects the operation output when block
stop is executed.
• On: Retains the on or off status of the coil
used in the operation output of the step,
which was being executed at the time of
block stop.
• Off: Turns off all the coil outputs.
(Operation output by the SET instruction
is retained regardless of the on/off status
of SM1196.)
Switches I/O numbers between the fuse-
blown module registers (SD1100 to
SD1107) and I/O module verify error
registers (SD1116 to SD1123) according to
the on/off combination of SM1197 and
SM1198.
• Recovers the setting data stored in the
CPU module at restart when sampling
trace/status latch is executed.
• Turn this on to re-execute the sampling
trace or status latch. (Rewriting data
using the programming tool is not
required.)
APPENDICES
Corresponding
A
CPU
Qn(H)
QnPH
Qn(H)
QnPH
Qn(H)
QnPH
483

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents