Overload Restriction Source Changeover

This function allows you to change the parameter sets of overload restriction. (Please
refer to chapter 3 for the detailed description of the overload restriction function.)
Option
Terminal
Code
Symbol
OLR
Overload restriction
39
source changeover
C001~C007
Valid for inputs:
b021~b026
Required settings
Torque Limit Selection
This function is to select the torque limit mode. (Please refer to chapter 3 for the
detailed description of the function.)
Option
Terminal
Code
Symbol
TL
Torque limit
40
selection
C001~C007
Valid for inputs:
b040~b044
Required settings
Function Name
State
ON
OFF
Function Name
State
ON
OFF
Description
Parameter sets b024, b025,
Parameter sets b021, b022,
Example (default input configuration shown—see
page
3–84):
7
6
5
4
3
See I/O specs on
page 4–6.
Description
B040
value is enabled as torque limit level
B040
value is disabled
Example (default input configuration shown—see
page
3–84):
7
6
5
4
See I/O specs on
page 4–6.
4−37
b026
are enabled.
b023
are enabled.
OLR
2
1
L PCS P24
TL
3
2
1
L
P24
PLC
PCS