Low Load Detection Parameters - Hitachi WJ200 Series Instruction Manual

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

3−94

Low Load Detection Parameters

The
following
conjunction with the intelligent output
function, when configured. The output
mode parameter (C038) sets the mode of
the detection at which the low load
detection signal [LOC] turns ON. Three
kinds of modes can be selected. The
detection level parameter (C039) is to set
the level of the low load.
This function is for generating an early
warning logic output, without causing
either a trip event or a restriction of the
motor current (those effects are available
on other functions).
Func.
Code
Output mode of low
C038
current detection
Low current detection
C039
level
parameters
work
"C" Function
Name
Two option codes:
00...During acceleration,
deceleration and constant speed
01...During constant speed only
Set the level of low load detection,
range is 0.0 to 2.0*inverter rated
current
in
Output
current
C039
0
[LOC]
output
1
0
Description
ON
Defaults
Run
Mode
Lnitial data
Units
Edit
01
INV rated
current
t
t
A