Network Communications Settings

The following table lists parameters that configure the inverter's serial communications
port. The settings affect how the inverter communication with a digital operator (such
as SRW-0EX), as well as a ModBus network (for networked inverter applications). The
settings cannot be edited via the network, in order to ensure network reliability. Refer to
"ModBus Network Communications" on page B-1 for more information on controlling
any monitoring your inverter from a network.
Func.
Code
Communication speed
C071
Modbus address
C072
Communication parity
C074
Communication stop bit
C075
Communication error
C076
select
Communication error
C077
time-out
Communication wait
C078
time
Communication speed
C071
"C" Function
Name
Eight option codes:
03...2,400 bps
04...4,800 bps
05...9,600 bps
06...19,200 bps
07...38,400 bps
08...57,600 bps
09...76,800 bps
10...115,200 bps
Set the address of the inverter on
the network. Range is 1 to 247
Three option codes:
00...No parity
01...Even parity
02...Odd parity
Two option codes:
1...1 bit
2...2 bit
Selects inverter response to
communications error.
Five options:
00...Trip
01...Decelerate to a stop and trip
02...Disable
03...Free run stop (coasting)
04...Decelerates to a stop
Sets the communications
watchdog timer period.
Range is 0.00 to 99.99 sec
0.0 = disabled
Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms
Eight option codes:
03...2,400 bps
04...4,800 bps
05...9,600 bps
06...19,200 bps
07...38,400 bps
08...57,600 bps
09...76,800 bps
10...115,200 bps
Description
Run
Defaults
Mode
Lnitial data
Units
Edit
05
baud
1.
00
1
02
0.00
0.
msec.
05
baud
bit
sec.