Motor Cable Length Parameter - Hitachi WJ200 Series Instruction Manual

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

3−54
Func.
Code
Software lock mode
B031
selection
NOTE: To disable parameter editing when using B031 lock modes 00 and 01, assign the
[SFT] function to one of the intelligent input terminals.
See "Software Lock" in chapter 4

Motor Cable Length Parameter

To achieve higher motor control performance, the WJ200 inverter has the Motor Cable
Length Parameter setting B033. Normally there is no need to adjust this parameter,
however in case of long motor cable and/or shielded cable, where there is a
comparatively higher earth capacitance, set this parameter higher to achieve better
motor control performance.
Note that the parameter is indicative and no formula to calculate the suitable value.
Normally, longer the motor cable, bigger the set value. Please adjust depending on your
system.
For 11 and 15kW inverter, it is not needed to set b033.
Func.
Code
Motor cable length
B033
parameter
"b" Function
Name
Prevents parameter changes, in
five options, option codes:
00...all parameters except B031
are locked when [SFT] terminal
is ON
01...all parameters except B031 and
output frequency F001 are locked
when [SFT] terminal is ON
02...all parameters except B031 are
locked
03...all parameters except B031 and
output frequency F001 are locked
10...High level access including B031
See appendix C for the accessible
parameters in this mode.
"b" Function
Name
Set range is 5 to 20.
Description
Description
Run
Defaults
Mode
Lnitial data
Units
Edit
01
Run
Defaults
Mode
Lnitial data
Units
Edit
10.