"C" Group: Intelligent Terminal Functions

The seven input terminals [1], [2], [3], [4], [5], [6], and [7] can be configured for any of 72
different functions. The next two tables show how to configure the seven terminals. The
inputs are logical, in that they are either OFF or ON. We define these states as OFF=0,
and ON=1.
The inverter comes with default options for the seven terminals. These settings are
initially unique, each one having its own setting. Note that European and US versions
have different default settings. You can use any option on any terminal, and even use
the same option twice to create a logical OR (though usually not required).
NOTE: Terminals [3] and [4] have the ability to be logical inputs, and to be safety inputs
in case of safe stop function is selected.
NOTE: Terminal [5] has the ability to be a logical input, and to be an analog input for a
thermistor device when PTC function (option code 19) is assigned to that terminal.
Input Terminal Configuration
Functions and Options – The
seventy-two options to any of the seven logic inputs for the XJ200 inverters. The
functions C001 through C007 configure the terminals [1] through [7] respectively. The
"value" of these particular parameters is not a scalar value, but it is a discrete number
that selects one option from many available
For example, if you set function C001=00, you have assigned option 00 (Forward Run) to
terminal [1]. The option codes and the specifics of how each one works are in Chap. 4.
Func.
Name
Code
Input [1] function
C001
Input [2] function
C002
Input [3] function
C003
[GS1 assignable]
Input [4] function
C004
[GS2 assignable]
Input [5] function
C005
[PTC assignable]
Input [6] function
C006
Input [7] function
C007
The input logic conversion is programmable for each of the seven inputs default to
normally open (active high), but you can select normally closed (active low) in order to
invert the sense of the logic.
function codes
"C" Function
Description
Select input terminal [1] function,
68 options (see next section)
Select input terminal [2] function,
68 options (see next section)
Select input terminal [3] function,
68 options (see next section)
Select input terminal [4] function,
68 options (see next section)
Select input terminal [5] function,
68 options (see next section)
Select input terminal [6] function,
68 options (see next section)
Select input terminal [7] function,
68 options (see next section)
in the following table let you assign one of
options
.
Run
Mode
Edit
3−83
Defaults
Lnitial data
Units
00
[FW]
01
[RV]
02
[CF1]
03
[CF2]
09
[2CH]
18
[RS]
13
[USP]