Programmer disconnect assemblies are available in two configurations, namely:
e
12-pin configuration. If the legacy LVS has a 12-pin programmer disconnect in use,
the same can be used with the Retrofill breaker. In this case, only the breaker side
programmer
disconnect
assembly
on the
breaker
needs
to be installed.
The
numbers for the programmer disconnects are mentioned below.
e
19-pin configuration-If the legacy LVS doesn't have a 12-pin programmer disconnect
configuration, and the customer chooses to install a programmer disconnect, then
the
19-pin
programmer
disconnect
assembly
needs
to
be
installed
in
the
compartment and the breaker.
12-Pin Programmer Disconnect Breaker Side
2TSE431952R1000
PROG.DIS.ASSY, AKD8
AKR30H/50H/TS50H AKD8
2TSE431953R1000
PROG. DIS. ASSY
AKR30S
2TSE431954R1000
PROG. DIS. ASSY
AKR?5/100/125
19-Pin Programmer Disconnect Breaker & compartment Side
2TSE431946R1000
PROG.DIS.ASSY, AKD8
AKR30H/50H/T50H AKD8
2TSE431947R1000
PROG.DIS.ASSY, AKR30S
AKR30S
2TSE431950R1000
PROG.DIS.ASSY, AKR75/100/125
AKR75/100/125
3.
If applicable, remove the existing compartment side programmer disconnect assembly.
The programmer disconnect assembly must be removed, if:
e
A 9-pin manual programmer disconnect assembly is installed in the cabinet as a
result of conversion kit.
©
A 24-pin
programmer
disconnect
assembly
is installed in the cabinet original
MicroVersaTrip ~1979-1984.
e
Customer chooses to replace a 12-pin configuration with a 19-pin configuration to
Add RELT
4.
Before uninstalling the existing programmer disconnect assembly, verify that the wiring
details match the wiring numbers. Any changes or deviations need to be noted for use
while installing the new programmer disconnect.
5.
Check that the compartment is de-energized and is safe to work in; and that the legacy
breaker has been removed from the cabinet.
6.
Disconnect the wires connecting the terminal block to the compartment Programmer
disconnect assembly. See Figure 51.
7.
If the customer
has chosen
to install a 19-pin
programmer
disconnect
assembly,
Replacing A 12-pin programmer disconnect assembly, the terminal block mounted on
the compartment needs to be removed as well. This can be achieved by unfastening the
two screws securing the terminal block with the side wall of the compartment.
8.
Unfasten the four bolts included that the hold the programmer disconnect assembly on
the wall of the compartment to remove the compartment-side programmer disconnect
assembly.
Figure 51
AKD-8, Loosen Hardware for the Programmer Disconnect Assembly
'
tn 7
fe
e e
Bolts |
/\/
Wires NI
ry
Programmer
Disconnect
Terminal,
:
Screws
>
est
Wires
Hl
i
oe
Terminal
Wires ~| |
L
iit
|
Screws = Programmer},
j
Disconnect
va
AKO8 Compartment