Modify AKD-8—AKR30S Switchgear Compartment only.
Danger
e
It must be ensured that the supply power to the
a
compartment is turned off/ compartment is de-
explosion hazards
energized
for all the
incoming
and
outgoing
pets
Po
circuits of the Low Voltage Switchgear prior to
any work being conducted on it.
e
During the installation and related work on the
tasks.
e
Ensure only qualified personnel install, operate, service, and maintain all electrical
equipment.
24-
AKD-8, AKR-30S Remove Glastic Sheet of compartment
.
Remove Glastic Sheet for AKR 30S only
Figure 30
Remove
glastic
sheet
The AKD-8 AKR30S switchgear compartments need this particular attention.
The glastic sheet has to be removed (Figure 30).
In some cases, however, it is possible that this sheet is not secured to the top of the cabinet
properly, and was found to sag around the middle of the cabinet. This could lead to the sheet
interfering with secondary disconnects. Resecure it to the top of campartment or replace it
with any UL recognized reinforced polyester glass sheet.
28] © 2020 Emax 2 Retrofill Circuit Breakers 800-5000A