Figure 38. Racking Assembly Inside Switchgear Compartment (w/no breaker)
23. Insert a screwdriver in the slot or rack-out lock, and turn it clockwise 90° so that the racking handle
shutter opens and insert the racking tool. (It resembles a vehicle ignition lock. See
Figure 39. Shutter
24. Insert the tool so it engages the racking mechanism inside the hole.
25. Then, crank clockwise so that the breaker starts to move in, slowly sliding forward.
Rotating clockwise ~ 37 turns racks the circuit breaker all the way into the cassette.
32 EntelliGuard R Circuit Breaker Retrofill AKD-5 Installation Manual
Figure
39.)
DEH-41547