Panasonic PAW-160MAH3M Installation Instructions Manual page 88

Air handling unit kit
Table of Contents

Advertisement

Parameter settings
Code No.
9
88
Item
12
System address (= address of outdoor unit)
13
Indoor unit address
14
Group control address
15
Temperature sensors
17
Cooling intake temperature shift
18
Automatic stop time after operation start
1C
Cooling discharge temperature shift
1d
Heating discharge temperature shift
1E
Temperature shift for cooling/heating change
in auto heat/cool mode
1F
Cooling upper limit T set
20
Cooling lower limit T set
21
Heating upper limit T set
22
Heating lower limit T set
23
Drying upper limit T set
24
Drying lower limit T set
25
Auto mode upper limit T set
26
Auto mode lower limit T set
28
Automatic power failure recovery
2A
Filter FI1 & FI2 (CN70) input switching
2C
Indoor unit electronic control valve
Data
Description
0001 ... 0030
Outdoor unit address 1 ... 30
0099
Not set
0001 ... 0064
Indoor unit address 1 ... 64
0099
Not set
0000
Individual (1:1 = AHU with no group wiring)
0001
Main unit (One of the group-control indoor units)
0002
Sub unit (All group-control indoor units except for main unit)
0099
Not set
0022
PACi default: TA, E1, E2
0029
ECOi default: TA, BL, E1, E3
0000
No offset (factory default)
-010 ... 0010
Makes an offset for the intake temperature by the set value in °C
during cooling mode
0000
Function disabled
0001 ... 0125
Stop time = set value * 5 minutes (example 0004 = operation stop
after 20 minutes)
0000
No offset (factory default)
-010 ... 0010
Makes an offset for the target blow out temperature limit for
thermostat off while discharge control enabled (code 3A) by the
set value in °C during cooling mode
0000
No offset (factory default)
-010 ... 0010
Makes an offset for the target blow out temperature limit for
thermostat off while discharge control enabled (code 3A) by the
set value in °C during heating mode
0001 ... 0007
Set value in °C for switch over hysteresis between cooling and
heating mode while AUTO mode being active
-015 ... 0060
Set limit value range in °C. Factory default = 0030 (30°C)
-015 ... 0060
Set limit value range in °C. Factory default = 0018 (18°C)
-015 ... 0060
Set limit value range in °C. Factory default = 0030 (30°C)
-015 ... 0060
Set limit value range in °C. Factory default = 0016 (16°C)
-015 ... 0060
Set limit value range in °C. Factory default = 0030 (30°C)
-015 ... 0060
Set limit value range in °C. Factory default = 0018 (18°C)
-015 ... 0060
Set limit value range in °C. Factory default = 0027 (27°C)
-015 ... 0060
Set limit value range in °C. Factory default = 0017 (17°C)
0000
No automatic recovery
0001
With automatic recovery
0000
Filter input (differential pressure switch input)
0001
Alarm input (for trouble input about air cleaner or similar device)
0002
Humidifier input (Operates linked with drain pump when humidi-
fier is ON.)
0000
VRF (ECOi) R410A
0002
PACi (R410A)
0004
VRF (ECOi) R32
0006
PACi (R32)
0008
VRF (ECOi) R32
AHU Kit – Installation Instructions – 07/2023