Panasonic PAW-160MAH3M Installation Instructions Manual page 56

Air handling unit kit
Table of Contents

Advertisement

Electrical Wiring
Terminal No.
X4
TA1
X4.1
l
TA2
X4.2
l
l
E1.1
X4.3
E1.2
X4.4
l
E3.1
X4.5
l
l
E3.2
X4.6
BL1
X4.7
l
BL2
X4.8
l
l
OP1
X4.9
OP2
X4.10
l
OP3
X4.11
l
l
OP4
X4.12
OP5
X4.13
l
OP6
X4.14
l
5
l
MO1
X4.15
MO2
X4.16
l
MO3
X4.17
l
l
MO4
X4.18
MO5
X4.19
l
Terminal No.
X5
l
U1
X5.1
U2
X5.2
l
R1
X5.3
l
l
R2
X5.4
To be continued on next page.
56
Allocation
Function
No polarity
Suction Temperature Sensor TA input (included)
(Room Temperature Sensor)
No polarity
No polarity
Sensor E1 / TH2 input
(included)
No polarity
No polarity
Sensor E3 / TH4 input
(included)
No polarity
No polarity
Discharge Temperature Sensor BL
Input (included)
No polarity
COM for OP2 - OP6 Higher
+ 12 V DC
Potential
Lower Potential for Defrost
Defrost signal output
Lower Potential for Thermostat
Thermostat ON signal output
ON
Lower Potential for Cool
Cool operation signal output
Operation
Lower Potential for Heat
Heat operation signal output
Operation
Lower Potential for Fan Mode
Fan mode (free cooling) operation signal output
Operation
ORG
RED
YEL
Expansion valve output
BLK
GRY / WHT
Allocation
Function
No polarity
Communication bus wiring P-link
No polarity
No polarity
Terminal for Group Wiring (RC connection)
No polarity
Description
Air temperature sensor
Refrigerant temperature sensor
Refrigerant temperature sensor
Air temperature sensor
12 V DC relay required for each signal output, field supplied
Description
Required for communication with outdoor unit and centralised
controller
Internal Potential: 16 V DC between R1 & R2
AHU Kit – Installation Instructions – 07/2023

Advertisement

Table of Contents
loading

This manual is also suitable for:

Paw-280mah3mPaw-560mah3mPaw-280pah3m-1

Table of Contents