Parameter settings

On how to access the "Detailed settings" mode, please see →
with AHU Kit capacity – Method C – steps 1 to 3, p. 48
Bluetooth connection with CZ-RTC6BL, see the manual of the "Panasonic H&C Control App" or the
service manual of PACi NX outdoor units, chapter 6.
Code No.
03
04
05
06
0A
0b
0C
0d
0E
0F
10
11
AHU Kit – Installation Instructions – 07/2023
Item
Central control address
Operating mode priority change
Fan speed when heating thermostat is OFF
Heating intake temperature shift
RC sensor differential
Function of EX1 & EX2 terminal
Display of cold wind protection
AUTO mode cooling/heating
Mode dependency (3way)
Cooling Only
Type
AHU unit capacity
4.4 Matching outdoor unit capacity
in this document, or in case of using the
Data
Description
0001 ... 0064
Central control address 1 ... 64
(only required in case of centralised controllers)
0099
Not set (Factory preset)
0000
Normal (Factory preset)
0001
Priority (only relevant for ECOi)
0000 ... 0002
While compressor ON or OFF → fan output signal ON (do not
0004 ... 0006
use 0003 or 0007 as this would cause fan stop while compressor
operating, dangerous!)
0008 ... 0010
While compressor ON → fan output signal ON
While compressor OFF → fan output signal OFF
0011
While compressor ON or OFF → fan output signal OFF
(take care when using this setting!)
0000
No offset
0001 ... 0006
Makes an offset for the intake temperature by the set value in °C
during heating mode
0000
Thermostat OFF differential: −1°C (setting at time of shipping)
0001
Thermostat OFF differential: −0.5°C
0000
AHU thermostat OFF (factory preset mode) when closed
0001
AHU shows "P14" alarm and transmits the refrigerant leakage
signal when closed
0000
Displayed on RC
0001
Not displayed
0000
Permit
0001
Prohibit
0000
Normal
0001
Same mode of main indoor unit in case of sharing valve kit in
3way systems
0000
Normal
0001
Cooling only operation (heat mode prohibited)
0033
AHU DX-kit
0000
Not set
0001
2,2 kW nominal cooling
0003
2,8 kW nominal cooling
0005
3,6 kW nominal cooling
0007
4,5 kW nominal cooling
0008
5,0 kW nominal cooling
0009
5,6 kW nominal cooling
0010
6,3 kW nominal cooling
0011
7,1 kW nominal cooling
0012
8,0 kW nominal cooling
0013
9,0 kW nominal cooling
0015
11,2 kW nominal cooling
0017
14,0 kW nominal cooling
0018
16,0 kW nominal cooling
0021
22,4 kW nominal cooling
0023
28,0 kW nominal cooling
0028
56,0 kW nominal cooling