Terminal Board Layout; Mah3 Models - Panasonic PAW-160MAH3M Installation Instructions Manual

Air handling unit kit
Table of Contents

Advertisement

5.3

Terminal board layout

5.3.1 MAH3 models

Terminal layout – Main terminal board (PAN.UXRP71B-P)
Allocation
Terminal No.
X1
L
X1.1
Live
l
N
X1.2
Neutral
l
l
PE
X1.4
Protective earth
Allocation
Terminal No.
X2
F1
X2.1
COM for F2
l
l
F2
X2.2
Fan contact
OP3
X2.3
Fan Alarm
l
K2
X2.4
Potential for OP3
l
l
HU1
X2.5
Humidifier contact
HU2
X2.6
COM for HU1
l
Allocation
Terminal No.
X3
l
FS1
X3.1
Lower Potential for FS
FS2
X3.2
Higher Potential for FS
l
FD1
X3.3
Higher Potential for ext.Fan
l
l
FD2
X3.4
Lower Potential for ext. Fan
EX1
X3.5
Higher Potential for EXCT
l
EX2
X3.6
Lower Potential for EXCT
l
Higher Potential for Filter
l
FI1
X3.7
Contact
Lower Potential for Filter
FI2
X3.8
l
Contact
T10.1
X3.9
Higher Potential for T10
l
l
T10.2
X3.10
Lower Potential for T10
To be continued on next page.
AHU Kit – Installation Instructions – 07/2023
Function
Live Terminal
Neutral Terminal
Protective Earth Conductor
Function
Fan Operation Signal
Fan Alarm Signal Input
(Unit will only operate if this contact is closed, otherwi-
se error code P01 will be displayed.)
External Humidifier Control output
Function
Float switch
(ex factory bridged)
ON/OFF Control output of an additional external fan or
additional external air handling unit
EXCT-Contact input
(external thermostat off switch)
Filter Contact input
(for external filter signal)
AHU ON/OFF external input
(Pulse: each pulse change start/stop; Static: closed =
ON, open = STOP)
Electrical Wiring
Description
External Potential: 230 V AC, max. 1 A
Description
External Potential: max. 250 VAC 8 A
Internal potential 230 VAC
Internal potential 230 VAC / max. 3A
Description
Internal Potential: 12 V DC
Internal potential: 12 V DC
Internal Potential: 5 V DC
Internal Potential: 5 V DC
Note: For activating filter input, verify in Detailed Settings that
code 2A is set to "0000"
Internal Potential: 5 V DC
Note: In Detailed Settings verify that code 2E is set to "0000".
Default pulse signal. For static signal cut JP001 on main PCB.
5