Peak Cut Operation; Peak Cut Operation Setting - Fujitsu AIRSTAGE UTY-ALGX Instruction Manual

System controller lite for vrf system
Table of Contents

Advertisement

25-4

Peak cut operation

555555

Peak cut operation setting

This function can reduce the electricity energy by setting a specific target value (maximum average power) at
all units to limit operation, make the detail target value will not be exceed.
Set a target value of average electricity [kW]in 60 minutes, and control the air condition not to exceed the
target value.
Set the upper limit power and the target power for up to 4 time period.
Temperature shift pattern is also set for each energy saving groups.
To display this screen, select main screen menu →"Setting" →"Energy Saving Group Setting".
Set the peak cut control to be "Active" or "Not Active".
Check the checkbox to decide a use target electricity. The checked items must be set.
Start Time, End Time
Upper Power Limit (kW)
Safety Margin (%)
Target Power (kW)
Set start time and end time for up to 4 time slots.
The checked time slots must not overlap each other, and the
total of the checked time slots must cover 24 hours of one day.
The value to have added the safety ratio (10%~50%) on the
target power.
Upper electricity will update automatically in accordance with
input selected value of target electricity.
The electricity of a target of peak cut control.0~10000kW.