Setting Name
SYNC01_SYNCHK1EN
SYNC01_TSYN
SYNC01_TSYN2
SYNC01_Split_EN
SYNC01_SYNCTEST
Input
DPSY01 (Function ID: 511001)
From DPSY01
511001 8B02011E48
DPSY01_OEC_RCV
SYNCHK1 (Function ID: 560001)
From SYNCHK1
560001 850B011F59
SYNC01_SYN_CLC
SYNCHK_Ry (Function ID: 561081)
From SYNCHK_Ry1
ΔV1
SyncRy1-dV
On
Δf1
SyncRy1-df
SyncRy1-dfEN
ΔƟ1
SyncRy1-dƟ
SyncRy1-Ɵ≈0
ΔƟ1≈0
SyncRy1-Ɵ less
ΔƟ1 less
From SYNCHK_Ry2
ΔV2
SyncRy2-dV
On
Δf2
SyncRy2-df
SyncRy2-dfEN
ΔƟ2
SyncRy2-dƟ
ΔƟ2≈0
SyncRy2-Ɵ≈0
SyncRy2-Ɵ less
ΔƟ2 less
PLC signals for relay selection relating to SYNCHK1
560001 800B01EDED
SYNC01_RY1_USE_STS
560001 800B01EDEE
SYNC01_RY2_USE_STS
PLC signals importation from external conditions
560001 800B01EDE2
SYNC01_SCL_F_ECP
560001 800B01EDE6
SYNC01_LPS_CL_ECP
560001 800B01EDE5
SYNC01_SPS_CL_ECP
560001 800B01EDE1
SYNC01_SBP_SSP
Figure 4.5-14 Synchronization check logic in SYNCHK1
Table 4.5-5 Synchronization settings in SYNCHK1
Description
SYNCHK1 synchronization checking enable
Synchronism check timer for synchronous
system
Timer to give up the synchronization
SYNCHK1 async. checking enable
Test in SYNCHK1 synchronism check
Close command (Operate)
SYNCHK1 (Function ID: 560001)
&
&
&
&
&
&
&
&
&
&
Bypassing condition
Off
SYNC01-SYNCHK1EN
SYNCHK logic in SYNCHK1
SYNC01_SCK_CS16
560001 880B011F6E
SYNC01_TSYN2
t
0
&
&
1
0.0 to 1800.0s
Check for synchronous network
SYNC01_SCK_CS04
560001 870B011F62
&
&
SYNC01_SCK_CS03
560001 860B011F61
&
SYNC01_SCK_CS02
560001 850B011F60
&
Check for asynchronous network
SYNC01_Ry_Ang_0Time
560001 870B011F77
&
SYNC01_Ry_Ang_RDC
560001 880B011F78
&
On
SYNC01-Split_SYN_EN
560001 800B01EDEB
- 610 -
6F2T0207 (0.01)
Default
Setting item or value
Off
On / Off
10s
0.00–100.00s
60s
30.0–1800.0s
Off
Off/On
Off
Off/On
SYNC01_SCK_CS01
560001 840B011F5F
SYNC01_SCK_CS09
SYNC01_LPS_CLC
560001 8C0B011F67
560001 840B011F58
SYNC01_TSYN
t
0
0.0 to 100.0s
SYNC01_SPS_CLC
560001 8D0B011F51
&
SYNC01_SBK_CSP
1
Blocking
GRE200 (5,6)
Output
560001 820B011F56
SYNC01_SCL_F
Sync Failed
To DPSY01
560001 850B011F59
SYNC01_SYN_CLC
&
Sync success
560001 800B011F54
SYNC01_SBP
Sync bypass