Multi functional protection ied

Advertisement

Command blocking*1 defined as "CBK")
Tripping *2 ("General trip")
Control hierarchy (e.g. 43RL) (PLC connection point #3)*4
543081 7019016D08
PWRQ_HHD_RSTREQ
IED serious error detected
Figure 4.3-10 Select condition logic for HHD&VAR resetting
Note: If tripping (GEN.TRIP in Table 4.3-5) is executed in the IED, any control
1
operation is blocked upon the trip operation. Tripping can be introduced by the
protection function if the IED has protection functions.
Note: Criteria "unmatched conditions" are decided when "Test-bit status" in command is
2
not identical to "IED test status".
Note: The user shall program the PLC logic "Control hierarchy condition". The Control
3
hierarchy condition provided by the user-programmed PLC logic may be 43R/L;
the user can connect it at PLC connection point "PWRQ_HHD_RSTREQ" of Table
4.3-5.
Receiving "Select command for VAR resetting" from the remote-end
(iii)
Logic and commands about VAR resetting are similar to the HHD ones. Read section (i) by
replacing "HHD" with "VAR" for the select command.
Select condition for VAR resetting
(iv)
Similarly, read section (ii) for the VAR select condition.
PWRQTY function (Function ID: 543081)
CBK_STATE
Unmatched condition detected *3
GEN. TRIP
Users must setup this condition correctly
SERI_ERR
[PWRQTY-EN]
On
1≥
- 565 -
6F2T0207 (0.01)
To selection logic
Select condition
&
&