Multi functional protection ied

Advertisement

Input
Command "Local-Off-Control"
ILK† condition ("Off") passed
DPOS01-Open
User configurable condition (PLC#3 connection point)
512001 800301EE56
DPOS01IN_TMP_34
User configurable condition
(PLC#2 connection point)
512001 820301EE5E
DPOS01IN_TMP_42
"DPOS01_FEC_OK_CSF"
Figure 4.2-26 Operate Off on the front panel in DPOS01
†Note: The ILK function can provide the operation criteria for "Off".
‡Note: An "operate condition" signal is generated in the operate-condition logic (see
Figure 4.2-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative "operate-condition" is required, it can be programmed by the user
and used to replace the signal generated by the original operate-condition logic.
The alternative "operate-condition" can be connected to the above logic using
connection point #3 "User configurable condition". That is, set the [DPOS01-
LGCTRCON] to PLC and use "DPOS01IN_TMP_34".
§§Note: The "DPOS01_OEX_BO" signal is issued when Fixedlogic is set for the scheme
switch [DPOS01-LGCFEXOT]. The "Operate completed" signal can also be issued
from the logic programmed by the user in place of the logic shown in Figure
4.2-20. The user-programmed logic is connected internally to the signal "Operate
completed", hence this signal is now generated by the user-programmed logic at
connection point #2 "User configurable condition". That is, set the scheme switch
[DPOS01-LGCFEXOT] to PLC and use "DPOS01IN_TMP_42".
*Note: The user can select a type of output signal. When Var is set for scheme switch
[DPOS01-PLSM], the output period of the signal is defined by the setting
[DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
Note: To identify the input and output signals of the other DPOS logics, see Table
††
Operate logic in DPOS01
DPOS1 function (Function ID: 512001)
Operate Cmd.
with ILK † condition
&
Operate Cmd.
without ILK † condition
[DPOS01-LGCTRCON]
Fixedlogic
Operate condition‡
[DPOS01-LGCFEXOT]
Fixedlogic
[DPOS01-PLSM]*
Var
Fix
Detection of state-change in a device
- 517 -
" DPOS01_FEC_OK_CS"
(512001 8003011E81)
1≥
1≥
&
&
&
&
&
1≥
&
&
6F2T0207 (0.01)
Output
" DPOS01_FEC_OK_CSF"
(512001 8003011E7E)
[DPOS01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"DPOS01_FEX_BO" §§
(512001 8103011DD0)
&
Assign to BOs
To "Wait for a command"
" DPOS01_EX_CMP "
( 512001 8003011E93 )
Operate Completed
" DPOS01_EX_FFL "
[DPOS01-RST]
(512001 8603011E91)
0
t
1.0s- 100.0s
Operate Failed
††
GRE200 (5,6)
††