ABB ACS880-207LC Hardware Manual page 65

Igbt supply units
Hide thumbs Also See for ACS880-207LC:
Table of Contents

Advertisement

If the outer surface of the shield is non-conductive:
Cut the shield at the midpoint of the peeled part. Be careful not to cut the
conductors or the grounding wire.
Turn the conductive side of the shield inside out over the insulation.
Cover the exposed shield and the peeled cable with copper foil to keep the shielding
continuous.
A
B
2
1
C
A
Stripped cable
B
Conductive surface of the shield exposed
C
Stripped part covered with copper foil
1
Cable shield
2
3
2
Copper foil
4
3
Shielded twisted pair
4
Grounding wire
Electrical installation 65