50 Electrical installation
1.
IP54 cabinet: Remove the rear horizontal cable support and the cable entry plate.
2.
IP54 cabinet: Remove a sealing grommet from the cable entry plate for each cable.
Cut hole into the rubber grommet and slide it onto the cable.
1
3.
Lead the cables inside the cabinet through the cable entry plate. If there are several
cables, use the rear 3 holes first.
IP54 cabinet: Attach the the sealing grommets to the cable entry plate. Attach
also the cable entry plate, and the cable support.
4.
For each cable, strip off 3...5 cm (1.2 ... 2 inches) of the outer insulation above the
cable entry plate. Strip also the end of the cable, and the end of the phase
conductors. Twist the shield to form a PE conductor, and mark it with yellow-green
tape or heat-shrink tubing.
5.
For each cable, attach cable lugs at the end of the PE conductor (twisted shield)
and phase conductors.
4
2
5