GE Multilin GEK-113328A Instruction Manual page 80

Generator protection & control system
Table of Contents

Advertisement

3.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE 3 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
3.1.8.6 RELAY CONFIGURATION
This is the relay configuration section in which the relay can be configured using internal states or already compiled
equation on PLC Editor.
Table 3–14: GENERAL OVERVIEW OF RELAY CONFIGURATION MENU:
3
RELAY CONFIG
3-20
Board F
Board located in first slot, always connected.
Board located in second slot, depends on model definition. If model is
Board G
type G0 there is no board in second slot.
Board H
Board located in first slot of CIO Module (external inputs/outputs module)
Board located in second slot of CIO Module (external inputs/outputs
Board J
module)
Outputs
Configuration of contact output operate and reset signals for all boards.
15 LEDs fully configurable from any logical variable, contact or virtual
input. First 5 LEDs are latched by hardware, the rest are self-reset but
LEDs
can be latched through PLC configuration. From the LED configuration
screen, it is possible to print the vertical LED label for the relay.
Configurable operations up to 24. Operation texts, interlocks, final states,
Operations
frontal keys, time outs and masters.
This tab allows assigning operands (logic signals) as inputs to different
Protection Elements
protection elements. To block, reset, initiate the different protection
elements inputs.
Trigger and up to 16 digital channels to be included in oscillography
records, are programmable from any logical variable, contact or virtual
input. Text configuration is only for off-line mode.
Oscillography
NOTE: This screen is used for the configuration of digital channels and
oscillography trigger. The rest of parameters, such as function enabling/
disabling, sampling rate, number of oscillography files, etc. must be set
on the Setpoint>Product Setup>Oscillography menu.
Up to 128 user programmable events from any logical variable, contact
or virtual input. Possibility to display the event as an alarm on the alarms
panel. Control events are also displayed in the snapshot events
Control Events
recording. 1 ms time tagging.
A control event is a logic signal associated to an operand or combination
of operands, that allows following the status of that signal.
Up to 16 configurable switchgear elements. A switchgear element can be
a breaker, a line selector switch, a grounding selector switch, a busbar
selector switch, etc. This screen allows configuration of type of contacts,
Switchgear
opening and closing time, contact assignation and text for events related
to switchgear. There are 64 pre-established events for switchgear, which
correspond to opening, closing, Error01 and Error11 of the 16
programmable switchgear elements.
Text configuration for off-line mode file management for all the contact
Inputs
inputs available in device.
Text configuration for off-line mode file management. 32 latched and 32
Virtual Inputs
self reset virtual inputs.
Screen for one line diagram configuration. This menu shows a scenario
MMI (HMI-Human
to draw a simplified one-line diagram of a bay in a feeder, line,
Machine Interface)
transformer, etc. The menu includes a library for power elements,
metering elements, text and drawings. See an example in
G650 Generator Protection & Control System
GEK-113328A