GE Multilin GEK-113328A Instruction Manual page 56

Generator protection & control system
Table of Contents

Advertisement

2.4 TECHNICAL SPECIFICATIONS
Protocols available:
Typical distance:
Isolation:
CAN PORT:
Rear port:
Type:
2
Fiber Wave length:
Fiber type:
Maximum recommended length
Isolation:
ETHERNET PORT:
Rear port:
Type (depending on model):
Model B:
Model C:
Model D:
Model E:
10/100BaseTX
100BaseFX
Wave length:
Fiber type:
Protocols available:
Typical distance:
Response time to ModBus commands: 10 ms Typical
Isolation:
In Models C and D, the 10/100BaseTX port is selected by an internal switch (see 3.3.3)
Two witness LED's for transmission and reception are included
2-30
®
ModBus
RTU / DNP 3.0
1200 m
2 kV
CAN port in models X, Y, Z for asynchronous rear ports
Multimode glass F.O. port with ST connectors
1300 nm
multimode 62.5/125 μm or 50/125 μm
500m
2 kV
COM3
10/100BaseTX self-negotiable
10/100BaseTX + 100Base FX
10/100BaseTX + redundant 100BaseFX (Physical media redundancy)
Redundant 10/100BaseTX self-negotiable ports
RJ45 connector
ST connectors
1300 nm
multimode 62.5/125 μm or 50/125 μm
ModBus® TCP/IP
DNP over TCP/IP and UDP/IP
Http, ftp, tftp (allow the use of a standard Internet browser)
1.65 km
2 kV
G650 Generator Protection & Control System
2 PRODUCT DESCRIPTION
GEK-113328A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multilin g650

Table of Contents