APPENDIX B
SETPOINT > CONTROL ELEMENTS > OVERFREQUENCY
OVERFREQUENCY 1 > OVERFREQUENCY 2 > OVERFREQUENCY 3
SETTING DESCRIPTION
Function permission
Pickup level
Trip time
Reset time
Minimum voltage threshold
Snapshot event generation
SETPOINT > CONTROL ELEMENTS > SYNCHROCHECK
SETTING DESCRIPTION
Function permission
Dead bus voltage level
Live bus voltage level
Dead line voltage level
Live line voltage level
Voltage Difference
Angle Difference
Frequency Slip
Breaker Closing time
Dead Line – Dead Bus Function
permission
Live Line – Dead Bus Function
permission
Dead Line – Live Bus Function
permission
Snapshot event generation
GEK-113328A
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
50.50
Trip Delay
0.00
Reset Delay
0.00
Minimum Voltage
30
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Dead Bus Level
10.00
Live Bus Level
50.00
Dead Line Level
10.00
Live Line Level
50.00
Max Volt Difference
10.00
Max Angle Difference 10.0
Max Freq Difference
20
Time
0.50
DL-DB Function
DISABLED
LL-DB Function
DISABLED
DL-LB Function
DISABLED
Snapshot Events
ENABLED
G650 Generator Protection & Control System
B.1 FACTORY DEFAULT SETTINGS
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 Hz
[20.00 : 65.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
1 V
[30 : 500]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 V
[0.00 : 500.00]
0.01 V
[0.00 : 500.00]
0.01 V
[0.00 : 500.00]
0.01 V
[0.00 : 500.00]
0.01 V
[2.00 : 500.00]
0.1 Deg
[2.0 : 80.0]
10 mHz
[10 : 5000]
0.01 s
[0.01 : 600.00]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
USER
VALUE
B
USER
VALUE
B-15