Hitachi ECO COMPACT PC-ARC-E Installation & Operation Manual page 81

Wired remote controller
Hide thumbs Also See for ECO COMPACT PC-ARC-E:
Table of Contents

Advertisement

Continue from previous page
Abnormality counter
Times of Abnormality
17
Times of Power
18
Failure
Times of Abnormal
19
Transmiting (Remote
controller - Outdoor unit)
Times of Inverter
20
Tripping
Control Information Display
Control Information
21
Pressure/Frequency
Discharge Pressure
22
Inlet Pressure
23
Control Information
24
Operating Frequency
25
(Hz)
Indoor unit capacity/Model/System number display
Indoor Unit
26
Capacity
Outdoor Unit
27
Model
System number
28
System number
29
Continue to next page
PMEN0630 rev.0 - 07/2022
E1
01
E2
00
E3
00
E4
00
F1
00
H1
18
H2
04
H3
44
H4
44
J1
08
J2
F 01
J3
01
J4
00
This number is incremented when transmission error occurs
between Wired Remote Controller and Indoor units and the
error remains for 3 minutes or longer.
The maximum count is 99. (99 is indicated for 99 or more)
For units without high pressure sensor, the value for H1 is a
control information. Unit is (×0.1MPa).
Value for unit A is shown for multi-type units.
For units without low pressure sensor, the value for H2 is a
control information. Unit is (×0.1MPa).
Value for unit A is shown for multi-type units.
Internal information of Wired Remote Controller is shown.
Operating frequency of the compressor is shown. (Max. number
for this item is 255)
For units without inverter compressor, the value for H4 is a
control information.
Indoor unit capacity code
Indication
Inverter types for tenants *2
F
(simultaneous operation unit (including single unit))
Multi-types (Cool and heat/Cooling only)
o1
Large floor type
L
Total Heat Exchanger
Inverter types for tenants
b
(independent operation unit (including single unit))
c
Cooling only units
E
Others
*1: n indicates the quantity of the indoor units that are connected to the system.
n=01-16
"E.00" is shown if communication error is occurred between indoor units and
outdoor units.
*2: For former outdoor units (models before 2010 April), "P" is shown.
J3:01-64 (Set the shipping status of RSW5 to 01 and decimal
representation)
J4:00-3F(Set the shipping status of RSW5 to 00 and hexadecimal
representation)
Model type
10
Code *1
F n
o1 n
L n
b n
c n
E n
67

Advertisement

Table of Contents
loading