3.1 Basics of I/O Allocation
Unit Type
(Note 1)
For using the user connections 17 to 216 by extending the number of user connections with the built-in
ET-LAN in the CPU unit, the above areas are used as flags confirming the transmission of the
communication instruction SEND/RECV. Change the starting number of the CPU unit or another unit
not to overlap I/O maps.
(Note 2)
The area for user connections 1 to 16 occupies four words including flags for general-purpose
communication.
(Note 3)
Occupied area in the area of user connections 17 to 216 varies according to the number of used
connections.
(Note 4)
The starting numbers of I/O contacts of each unit including the CPU unit can be changed by the
setting of tool software.
I/O Unit
Unit Type
Input unit 16 points
Input unit 32 points
Input unit 64 points
Output unit 16 points
I/O Unit
Output unit 32 points
Output unit 64 points
I/O Mixed Unit
Input: 32 points/Output:
32 points
3-4
Model No. or Function
17 to 32
33 to 48
49 to 64
65 to 80
81 to 96
97 to 112
User
113 to 128
connection
129 to 144
145 to 160
161 to 176
177 to 192
193 to 208
209 to 216
Product no.
AFP7X16DW
AFP7X32D2
AFP7X64D2
AFP7Y16R, AFP7Y16T
AFP7Y16P
AFP7Y32T, AFP7Y32P
AFP7Y64T, AFP7Y64P
AFP7XY64D2T
AFP7XY64D2P
Occupied words (occupied I/O points)
Input
WX11
WY11-WY12
WX13
WY13-WY14
WX15
WY15-WY16
WX17
WY17-WY18
WX19
WY19-WY20
WX21
WY21-WY22
WX23
WY23-WY24
WX25
WY25-WY26
WX27
WY27-WY28
WX29
WY29-WY30
WX31
WY31-WY32
WX33
WY33-WY34
WX35
WY35-WY36
Occupied words (occupied I/O points)
Input
1 words (16 points)
2 words (32 points)
4 words (64 points)
1 words (16 points)
2 words (32 points)
4 words (64 points)
2 words (32 points)
2 words (32 points)
WUME-FP7CPUH-09
Output
Output