8.1 CPU Unit Specifications
Device
Name
No.
Operation error occurrence
SD7
PB number (hold type)
Address with operation error
(hold type)
SD8
(32-bit lower address)
Address with operation error
(hold type)
SD9
(32-bit higher address)
Operation error occurrence
SD10
PB number (latest type)
Address with operation error
(new type)
SD11
(32-bit lower address)
Address with operation error
(new type)
SD12
(32-bit higher address)
SD13
(Not used)
-SD18
SD19
RING counter 2.5 ms
SD20
RING counter 10 μs
SD21
RING counter 100 μs
SD22
Scan time (current value)
SD23
Scan time (minimum value)
SD24
Scan time (maximum value)
SD25
(Not used)
-SD26
Interval for PB for execution
SD27
at a specified interval
SD28
(Not used)
(Note 1)
SD0 to SD5 are available only when the corresponding system relays SR0 to SR5 are on.
8-18
Description
Bit No.
1
2
3
4
5
6
Saves the PB number where the first operation error occurred after
the unit has started operating.
Saves the address where the first operation error occurred after the
unit has started operating. Perform monitoring using 32-bit data.
Saves the PB number where an operation error occurred. Every time
a new error occurs, the data are updated. The value '0' is recorded
at the start of the scan.
Saves the address where an operation error occurred. Every time a
new error occurs, the data are updated. The value '0' is recorded at
the start of the scan. Perform monitoring using 32-bit data.
The saved value is increased by one every time the respective time
unit has passed. (H0 to HFFFF)
Current values of SD19 to SD21 can only be read when SD19 to
SD21 are directly specified and read by MV instruction. The scan
start value is read by other instructions.
Saves the current
value.
[Saved value (decimal)] x 10 μs scan time
indication: Indicates operation cycle time in the
Stores the
RUN mode only. Max. and Min. values are
minimum value.
cleared at switching between the RUN mode
and the PROG. mode.
Saves the
maximum value.
Saves interval for PB for execution at a specified interval.
Description
FTPc settings
HTTPc settings
Mailc settings
EIP settings
W-PLC link settings
W2-PLC link settings