Huawei NetCol5000-C065 Quick Manual page 5

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C065:
Table of Contents

Advertisement

4
Installing Pipes
4.1
Pipe Layout
1. A 1:100 tilt should be reserved for the main drainpipe.
2. Keep a clearance of at least 25 mm between pipes. Secure the pipes to supports every a certain distance.
3. Clean the water inlet engineering pipes to avoid impurities entering into the humidifier.
4. A reducing valve must be installed if the inlet water pressure exceeds 0.7 MPa.
5. Pipes should be wrapped with thermal insulation foam along the route.
6. Condensate water can be drained from the top or bottom. Determine the appropriate pipe connection
based on site requirements.
After installing the condensate pump drainpipe (optional) and automatic drainpipe, connect them to
the main pipe and bind them with a cable tie according to step 1 in the figure. Then wrap the pipes
with tape or use other materials to secure them, as shown by step 2 in the figure.
Scenario
Pipes Must Be
Connected
Bottom
Auto-drainpipe
drainage
and water
pump drainpipe
4.2
Connecting the Drainpipe
Automatic drainpipe 1 Automatic drainpipe 2
Reserved port
for the automatic
drainpipe
Adapter
Rigid pipe
Automatic drainpipe
The automatic drainpipe can be connected in
two modes. The following figure illustrates
one mode.
Water pump drainpipe (optional)
Reserved port
for the
automatic
drainpipe
Pagoda
connector
Hose clamp
Hose
Water pump drainpipe (Optional)
5
Unit: mm
Reserved port for
the water pump
Hose clamp
Hose