Installing The Equipment - Huawei NetCol5000-C065 Quick Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C065:
Table of Contents

Advertisement

3

Installing the Equipment

1. Read the related user manual or instructions before installing the NetCol5000-C.
2. The unit in this document is a fully configured NetCol5000-C. If some components are not
configured, skip the corresponding steps.
3. You are recommended to use tools that are fully insulated when installing devices.
4. Only engineers from the manufacturer or engineers certified by the agent are allowed to install,
commission, and maintain smart cooling products. Otherwise, personal injuries and device
damage may be caused, which is beyond the smart cooling product warranty range.
3.1
Removing Air Filters
NOTE
There are two air filters for NetCol5000-C065
kW and three for NetCol5000-C080 kW. The
following figure uses the NetCol5000-C065
model as an example.
3.2
Discharging Nitrogen
1. The equipment has been injected with
0.3–0.5 MPa of nitrogen before delivery. If
no nitrogen is discharged, contact Huawei
technical support.
2. You can open or close the exhaust valve
using a flat-head screwdriver.
Slowly open the exhaust valve to release
nitrogen and close the valve afterwards.