Date And Time; Type Of Network - ABB M4M 30 User Manual

Network analyzer
Hide thumbs Also See for M4M 30:
Table of Contents

Advertisement

M4M 30 NETWORK ANALYZER USER MANUAL

6.3.Date and time

Setting date and time is mandatory in order to use the time-related functionalities on the device (e.g.
Historicals, Maximum, Minimum). Please notice that if no date and time are set, no timestamp will be
available on the measured data.
Unit
Menu
Set date
Set time

6.4.Type of network

In order to configure the type of network it is needed to choose one of the available options according to
the installation conditions.
Installation
2
According to the type of network that has been chosen, the parameters visualized on the device HMI
change.
Option
Description
3Ph/4W/4CT
3-phase 4-wire + 4CTs
3Ph/4W/3CT
3-phase 4-wire + 3CTs
3Ph/4W/1CT
3-phase 4-wire + 1CT
3Ph/3W/1CT
3-phase 3-wire + 1CT
Date/Time
Description
Configure the current date with format YYYY/MM/DD.
Configure the current time.
Type of network
1
Option
3Ph/3W/3CT
3Ph/3W/2CT
2Ph/3W/2CT
1Ph/2W/1CT
1. Scroll the list of fields
2. Select one option
Description
3-phase 3-wire + 3CTs
3-phase 3-wire + 2CTs
2-phase 3-wire + 2CTs
1-phase 2-wire + 1CT