M4M 30 NETWORK ANALYZER USER MANUAL
• Clock
Tariffs
Selecting Clock, it is possible to define when the different tariffs are active, according to specific day and
hour, driven by Real Time Clock.
After selecting a tariff (6 tariffs available), it is needed to configure the type of day of the tariff - during
the week or during the weekend.
Select the day type among one of the following options: None, Weekday, Weekend. In order to disable a
tariff, please select None.
If weekday or weekend is chosen, then the tariff will be enabled during the weekdays or during the
weekend, and it is needed to select the start hour of the tariff. Configure the start hour in the format
hh:mm.
Each tariff is kept active until the next tariff is activated, thus to define the end hour of each tariff set it as the
start hour of the following tariff in the same day type.
• Input
Tariffs
Selecting Input, the activation of the tariffs will follow the following table:
Input 1
Input 2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
Please see chapter "7.4 Inputs / Outputs" for further details on how to setup an I/O slot as Tariff input.
• Communication
Selecting Communication, the activation of the tariffs is controlled by bus.
It is possible control directly the activation of the individual tariffs. Multiple configuration settings
cannot be used.
Tariffs
See Modbus communication manual for details on how to read Tariff via communication.
Clock
Input
Input 3
OFF
OFF
OFF
OFF
ON
ON
Communication
Tariff
= T1
= T2
= T3
= T4
= T5
= T6