M4M 30 NETWORK ANALYZER USER MANUAL
Max/Min Demand menu
Max/min demand functionality is used to measure and store in the product flash memory the maximum
and minimum demand values referred to a specific time period (day, week, month) of main real time
measured. Demand values are calculated over a specific time interval (from 1 to 60 minutes). When the
last interval of an ongoing period has finished, the maximum and/or minimum values are stored together
with the timestamps, and a new period starts. Therefore, within the defined time period M4M will
provide the max/min demand values calculated over the time interval. It is possible to store also the 2nd
and the 3rd max/min. Max/min demand functionality allows to store up to the 3 highest and/or lowest
demand values per each parameter. Up to 25 parameters, thus up to 25 channels of flash memory can be
configured.
→
→
Historicals
Menu
Description
Time interval used for calculation of demand values that will be stored
Time interval
into the memory with timestamp.
Time period over which max and/or min values are evaluated and then
TIme period
stored.
Available channels in max/min demand. Each channel can be configured
Channels
to a defined parameter.
Please note that M4M allows to store 1 year of 3 highest and 3 lowest demand values with time interval of 30
min. and time period of day for 25 parameters (25 channels of memory).
→
Max/min demand
41