ABB M4M 30 User Manual page 41

Network analyzer
Hide thumbs Also See for M4M 30:
Table of Contents

Advertisement

M4M 30 NETWORK ANALYZER USER MANUAL
Max/Min Demand menu
Max/min demand functionality is used to measure and store in the product flash memory the maximum
and minimum demand values referred to a specific time period (day, week, month) of main real time
measured. Demand values are calculated over a specific time interval (from 1 to 60 minutes). When the
last interval of an ongoing period has finished, the maximum and/or minimum values are stored together
with the timestamps, and a new period starts. Therefore, within the defined time period M4M will
provide the max/min demand values calculated over the time interval. It is possible to store also the 2nd
and the 3rd max/min. Max/min demand functionality allows to store up to the 3 highest and/or lowest
demand values per each parameter. Up to 25 parameters, thus up to 25 channels of flash memory can be
configured.
Historicals
Menu
Description
Time interval used for calculation of demand values that will be stored
Time interval
into the memory with timestamp.
Time period over which max and/or min values are evaluated and then
TIme period
stored.
Available channels in max/min demand. Each channel can be configured
Channels
to a defined parameter.
Please note that M4M allows to store 1 year of 3 highest and 3 lowest demand values with time interval of 30
min. and time period of day for 25 parameters (25 channels of memory).
Max/min demand
41

Advertisement

Table of Contents
loading