Huawei UPS5000-H-400 kVA User Manual page 74

Hide thumbs Also See for UPS5000-H-400 kVA:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
Table 6-4 Power terminal connection requirements
Port
Connection Method
Mains input
Crimped DT terminal
Bypass input
Crimped DT terminal
Battery input
Crimped DT terminal
Output
Crimped DT terminal
PE
Crimped DT terminal
Equipotential
Crimped DT terminal
ground point
Table 6-5 Recommended input/output circuit breakers
Compone
Specificat
nt Name
a
ions
(200
kVA)
Mains
400 A/3P
input
circuit
breaker
Bypass
400 A/3P
input
circuit
breaker
Downstre
400 A/3P
am
output
circuit
breaker
a: recommended model when the short-circuit current where the circuit breaker is located is less
than 65 kA
Issue 02 (2021-04-22)
Conductor insulation: PVC insulation
The 90°C flexible cables with copper conductors are used.
It is recommended that AC power cables be no longer than 30 meters
and DC power cables be no longer than 50 meters.
Specificat
Specificat
a
ions
ions
(300
(400
kVA)
kVA)
630 A/3P
800 A/3P
630 A/3P
800 A/3P
630 A/3P
800 A/3P
Copyright © Huawei Technologies Co., Ltd.
Bolt
Specifications
M16
M16
M16
M16
M12
M6
Specificat
a
a
ions
(500
kVA)
1000
A/3P
1000
A/3P
1000
A/3P
Bolt Length
Torque
55 mm
120 N·m
55 mm
120 N·m
55 mm
120 N·m
55 mm
120 N·m
30 mm
47 N·m
12 mm
4.5 N·m
Specificat
Specificat
a
a
ions
ions
(600
(700
kVA)
kVA)
1250
1600
A/3P
A/3P
1250
1600
A/3P
A/3P
1250
1600
A/3P
A/3P
6 Installation
Specificat
a
ions
(800
kVA)
1600
A/3P
1600
A/3P
1600
A/3P
66