Inverter keeps output frequency unchanged.If this terminal is disabled, inverter will
continue traverse operation with current frequency.
21:Swing frequency reset
Reference frequency of inverter will be forced as center frequency of traverse
operation.
22:ACC/DEC forbid
ACC/DEC is invalid and maintains output frequency if it is enabled.
23:torque control forbid
Torque control is forbidden and switch inverter to run in speed control mode.
24:Counter trigger
The pulse input terminal of internal counter.Maximum pulse frequency:200Hz.
25:Counter clear zero
Clear the value of counter.
26:Frequency source switch
The power terminal is valid,frequency source combinations are forced to
switch,frequency source refer to Code F0.05.
27:HDI input
The terminal will be set to high speed pulse input(Only the HDI port effectively).
28:Motor switch
Using to switch the first motor and the second motor.
29:PLC status reset
Restart the process of simple PLC,removing previous state of PLC memory
information.
30:Running command switch to the terminals
This terminal is valid,running command is controlled by the terminal.
31:DC braking
This terminal is valid,inverter switch to Dc braking state,braking current is determined
by F1.09.
32ÿ^40:Reserved