Code
F0.18
0:No action
1:Parameters upload
According to save the parameters of the type on the operation panel (with or without
the motor parameters etc),automatically uploaded to the control panel.
2:Parameters downloadÿ allÿ
In addition to the historical record run (FU) parameters,other parameters downloaded
to EEPROM on the operation panel.
3:Parameters downloadÿ Except the motor parametersÿ
In addition to the running record (FU) and motor parameters group (F2),other
parameters downloaded to EEPROM on the operation panel.

6.2 F1 Group: Start and stop Control

Code
F1.00
0:Start directly: Start the motor at the starting frequency directly.
1:DC braking and start: Inverter will output DC current firstly and then start the motor at
the starting frequency(Pay attention to set the parameters of F1.03 and F1.04).It is
suitable for the motor which have small inertia load and may reverse rotation when start.
2: Speed tracking and start:Inverter detects the rotation speed and direction of
motor,then start running to its reference frequency based on current speed.This can
Name
Parameters copy
Name
Start mode
66
Setting Range
0ÿ^30 00
Setting Range
0ÿ^20 00