Craftsman G10-0R7G-2SB Manual page 69

Table of Contents

Advertisement

F1.10
DC braking initial frequency:Start the DC braking when running frequency reaches
starting
frequency determined.Starting frequency of DC braking is 0 and the DC braking is
invalid.The
inverter will stop in the defined DEC time.
DC braking waiting time:Before the start of the outage dc braking,inverter blockade
output, after the delay a restart dc braking.Used to prevent the high speed start over
current fault caused by dc braking.
DC braking current:Refers to add the amount of dc braking. The bigger braking current
is, the greater the braking torque is.
DC braking duration:Refers to the amount of dc braking sustain time.
Code
F1.11
DC braking duration
Fig.6-3 DC braking diagram
Name
FWD&REV dead time
69