Download Print this page

ABB REC670 Product Manual page 43

Relion 670 series, pre-configured
Hide thumbs Also See for REC670:

Advertisement

ABB
Bay control REC670
Pre-configured
Product version: 1.1
Table 21. Insulation
Test
Dielectric test
Impulse voltage test
Insulation resistance
Table 22. Environmental tests
Test
Cold test
Storage test
Dry heat test
Damp heat test, steady state
Damp heat test, cyclic
Table 23. CE compliance
Test
Immunity
Emissivity
Low voltage directive
Table 24. Mechanical tests
Test
Vibration response test
Vibration endurance test
Shock response test
Shock withstand test
Bump test
Seismic test
Type test values
2.0 kV AC, 1 min.
5 kV, 1.2/50 ms, 0.5 J
>100 MW at 500 VDC
Type test value
Test Ad for 16 h at -25°C
Test Ad for 16 h at -40°C
Test Bd for 16 h at +70°C
Test Ca for 4 days at +40 °C and
humidity 93%
Test Db for 6 cycles at +25 to +55
°C and humidity 93 to 95% (1 cycle
= 24 hours)
Type test values
Class II
Class I
Class II
Class I
Class I
Class II
1MRK 511 192-BEN B
Issued: June 2010
Reference standard
IEC 60255-5
Reference standard
IEC 60068-2-1
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-78
IEC 60068-2-30
According to
EN 50263
EN 50263
EN 50178
Reference standards
IEC 60255-21-1
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-2
IEC 60255-21-2
IEC 60255-21-3
43