Type tests according to standards
Table 20. Electromagnetic compatibility
Test
1 MHz burst disturbance
Ring wave immunity test
Surge withstand capability test
Electrostatic discharge
Direct application
Indirect application
Electrostatic discharge
Direct application
Indirect application
Fast transient disturbance
Surge immunity test
Power frequency immunity test
Conducted common mode
immunity test
Power frequency magnetic field test 1000 A/m, 3 s
Damped oscillatory magnetic field
test
Radiated electromagnetic field
disturbance
Radiated electromagnetic field
disturbance
Radiated electromagnetic field
disturbance
Conducted electromagnetic field
disturbance
Radiated emission
Conducted emission
42
Type test values
2.5 kV
2-4 kV
2.5 kV, oscillatory
4.0 kV, fast transient
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
4 kV
1-2 kV, 1.2/50 ms
high energy
150-300 V,
50 Hz
15 Hz-150 kHz
100 A/m
20 V/m, 80-1000 MHz
20 V/m, 80-2500 MHz
35 V/m
26-1000 MHz
10 V, 0.15-80 MHz
30-1000 MHz
0.15-30 MHz
1MRK 511 192-BEN B
Issued: June 2010
Reference standards
IEC 60255-22-1, Class III
IEC 61000-4-12, Class III
IEEE/ANSI C37.90.1
IEC 60255-22-2, Class IV
IEC 61000-4-2, Class IV
IEEE/ANSI C37.90.1
IEC 60255-22-4, Class A
IEC 60255-22-5
IEC 60255-22-7, Class A
IEC 61000-4-16, Class IV
IEC 61000-4-8, Class V
IEC 61000-4-10, Class V
IEC 60255-22-3
EN 61000-4-3
IEEE/ANSI C37.90.2
IEC 60255-22-6
IEC 60255-25
IEC 60255-25