Software
NOTICE
To activate parameter modifications the UPS program is automatically stopped
and restarted During this time (approx. 5 to 10 seconds) there is no monitoring.
COM Port:
In this group the serial communication interface is selected to which the UPS
is connected. If one or more serial interfaces are deactivated in the BIOS, Win‐
dows NT "numbers" the remaining interfaces. Therefore, a new interface has
to be selected in the configuration dialog under COM port. If no interface is
found during the start of the service, a corresponding dialog box opens and the
service is terminated.
The following settings can be made in the Advanced Controls group:
Shutdown Delay Time:
In this field a delay time for the shutdown from 0 to 45 seconds is defined. This
is the time the user has to backup his data. After the expiration of the delay time
all application programs are terminated without a prompt!
When defining the Shutdown Delay Time, observe that between the end of the
Shutdown Delay Time and the expiration of the 60 seconds after the power
down signal remains enough time to shut down the operating system (for clos‐
ing the Windows system files and generating backups). If the time is too short,
the shutdown process is interrupted, because the UPS interrupts the voltage of
the power supply unit. This can cause data loss.
NOTICE
Once the Shutdown Delay Time has been expired, the operating system is
shutdown without a prompt.
Enable Startup Battery Test:
If the Enable Startup Battery Test checkbox is activated, the battery pack is
checked during each restart. In error case an error dialog is generated and a
message is sent to the whole system. The UPS program is still running.
After 12 hours the battery test is automatically repeated:
If no further error occurs, the battery test is automatically repeated every
12 hours.
If an error occurs, an error dialog is generated, a message is sent to the
whole system and the UPS program is terminated.
Enable Temp Control:
If this checkbox is activated, the surrounding air temperature is monitored con‐
tinuously. If +50 °C are exceeded, a warning window is displayed and on the
device front the LED "Temp" flashes. The temperature warning can be switched
off.
For temperatures greater than +65 °C the system is always shut down and
switched off via the UPS logic.
The voltage monitoring is still active after a temperature warning.
Enable Fan Control:
DOK-SUPPL*-VPB*40.1***-PR02-EN-P
Rexroth IndraControl VPB 40.1 Control Cabinet PC
No monitoring (approx. 5 to 10 seconds) after
parameter modifications.
Data loss of of not saved data of opened ap‐
plication programs after expiration of the "Shut‐
down Delay Time".