Universal process indicator
Inputs
Maximum Range
Thermocouple
°C (°F)
–18 to 1800
#
B
(0 to 3270)
–100 to 900
E
(–140 to 1650)
–100 to 900
J
(–140 to 1650)
–100 to 1300
K
(–140 to 2350)
–100 to 900
L
(–140 to 1650)
–200 to 1300
N
(–325 to 2350)
–18 to 1700
#
R
(0 to 3000)
–18 to 1700
#
S
(0 to 3000)
–250 to 300
#
T
(–400 to 550)
#
For B, R, S and T thermocouples, accuracy is not guaranteed below
the value stated.
72
1
/
DIN
8
Accuracy
(% of reading)
0.1 % or ±2 °C (3.6 °F)
(above 200 °C [392 °F]) *
0.1 % or ±0.5 °C
(0.9 °F)
0.1 % or ±0.5 °C
(0.9 °F)
0.1 % or ±0.5 °C
(0.9 °F)
0.1 % or ±1.5 °C
(2.7 °F)
0.1 % or ±0.5 °C
(0.9 °F)
0.1 % or ±1 °C (1.8 °F)
(above 300 °C [540 °F])
0.1 % or ±1 °C (1.8 °F)
(above 200 °C [392 °F])
0.1 % or ±0.5 °C (0.9 °F)
(above –150 °C [–238 °F])
Maximum Range
RTD
°C (°F)
–200 to 600
PT100
(–325 to 1100)
Standard
Linear Inputs
Analog Input
Millivolts
0 to 150 mV
Milliamps
0 to 50 mA
Volts
0 to 25 V
Resistance  (low)
0 to 550 
Resistance  (high)
0 to 10 k
Sample Interval
125 ms per sample
10 Specification
Accuracy
(% of reading)
0.1 % or ±0.5 °C
(0.9 °F)
Accuracy
(% of reading)
0.1 % or ±20 µV
0.2 % or ±4 µA
0.2 % or ±1 mV
0.2 % or ±0.1
0.1 % or ±0.5