ControlMaster CM15
Universal process indicator
... Input/Output / ...Analog Input 1 (2)
Elect. Low
Elect. High
Linearizer
32
1
/
DIN
8
Sets the required electrical range.
Note. Applicable only to Millivolts, Milliamps, Volts and Ohms.
Linear Inputs
Standard Analog Input
Millivolts
Milliamps
Volts
Resistance
(low)
Resistance
(high)
Sets the required electrical range.
Note. Applicable only to Millivolts, Milliamps, Volts and Freq. Input.
Selects the linearizer type required to condition the input signal.
Notes. For thermocouple applications using an external fixed cold junction, set Input Type
to Millivolts (see page 31) and select the appropriate linearizer type.
Not applicable for Pulse Input, Digital volt-free, 24V Digital parameters – see page 31.
Accuracy (% of Reading)
0 to 150 mV
0 to 50 mA
0 to 25 V
0 to 550
0 to 10 k
7 Advanced Level
0.1 % or ±20 µV
0.2 % or ±4 µV
0.2 % or ±1 mV
0.2 % or ±0.1
0.1 % or ±0.5
IM/CM/I–EN Rev. D